Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2024-10-17 |
| TT | Health-based | Resolved | 2017-01-01 → 2017-01-31 |
| TT | Health-based | Resolved | 2017-01-01 → 2017-01-31 |
| TT | Health-based | Resolved | 1993-08-01 → 1993-08-31 |
| TT | Health-based | Resolved | 1993-08-01 → 1993-08-31 |
| RPT | Monitoring | Unaddressed | 2024-10-17 |
| MR | Monitoring | Resolved | 2017-10-01 |
| MR | Monitoring | Resolved | 2017-10-01 |
| MR | Monitoring | Resolved | 2005-11-01 → 2005-11-30 |
| MR | Monitoring | Resolved | 1996-08-01 → 1996-08-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 660 µg/L 6.6% of the EPA limit 10000 µg/L | 16/24 | SYR4 | 2012–2019 |
| Bromodichloromethane | 15.7 µg/L No EPA limit set
worst single sample: 17 µg/L | 14/14 | SYR4 | 2015–2019 |
| Chloroform | 89.75 µg/L No EPA limit set
worst single sample: 93 µg/L | 14/14 | SYR4 | 2015–2019 |
| Dibromochloromethane | 3.51 µg/L No EPA limit set
worst single sample: 3.9 µg/L | 14/14 | SYR4 | 2015–2019 |
| Dichloroacetic Acid | 32.2 µg/L No EPA limit set
worst single sample: 40 µg/L | 14/14 | SYR4 | 2014–2019 |
| TTHM | 103.5 µg/L 129% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 110 µg/L | 14/14 | SYR4 | 2015–2019 |
| Total Haloacetic Acids (HAA5) | 81.8 µg/L 136% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 100 µg/L | 14/14 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 50.6 µg/L No EPA limit set
worst single sample: 61 µg/L | 14/14 | SYR4 | 2014–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2024 |
| Fluoride | 362 µg/L 9% of the EPA limit 4000 µg/L
worst single sample: 370 µg/L | 9/9 | SYR4 | 2012–2019 |
| Barium | 47.95 µg/L 2.4% of the EPA limit 2000 µg/L
worst single sample: 49 µg/L | 8/8 | SYR4 | 2012–2019 |
| Arsenic | 0.7720 µg/L 7.7% of the EPA limit 10 µg/L
worst single sample: 0.8100 µg/L | 5/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.07 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 4/14 | SYR4 | 2014–2019 |
| Lead | 0.9360 µg/L 6.2% of the EPA limit 15 µg/L
worst single sample: 1 µg/L | 3/8 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 117066 µg/L 1171% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 130000 µg/L | 3/7 | SYR4 | 2012–2019 |
| Chromium | 1.372 µg/L 1.4% of the EPA limit 100 µg/L
worst single sample: 1.4 µg/L | 2/8 | SYR4 | 2012–2019 |
| Selenium | 1.5 µg/L 3% of the EPA limit 50 µg/L | 1/8 | SYR4 | 2012–2019 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Raineri Mutual Water Company
Is Raineri Mutual Water Company tap water safe to drink?
EPA monitoring detected 17 contaminants in Raineri Mutual Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Raineri Mutual Water Company's water?
EPA monitoring detected Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Raineri Mutual Water Company serve?
Raineri Mutual Water Company reports serving 145 people in California, per its EPA record.
Has Raineri Mutual Water Company had any water quality violations?
The EPA has 12 violations on file for Raineri Mutual Water Company, of which 5 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.