Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| TT | Health-based | Resolved | 2017-06-26 |
| TT | Health-based | Resolved | 2017-06-26 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-03-01 → 2016-03-31 |
| MCL | Health-based | Resolved | 2016-03-01 → 2016-03-31 |
| MCL | Health-based | Resolved | 2014-11-01 → 2014-11-30 |
| MCL | Health-based | Resolved | 2014-11-01 → 2014-11-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 758 µg/L 19% of the EPA limit 4000 µg/L
worst single sample: 840 µg/L | 193/195 | SYR4 | 2012–2019 |
| Nitrate | 1900 µg/L 19% of the EPA limit 10000 µg/L
worst single sample: 2712 µg/L | 180/394 | SYR4 | 2012–2019 |
| TTHM | 91.05 µg/L 114% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 140 µg/L | 180/197 | SYR4 | 2012–2019 |
| Bromoform | 23.45 µg/L No EPA limit set
worst single sample: 39 µg/L | 172/200 | SYR4 | 2012–2019 |
| Dibromochloromethane | 39.5 µg/L No EPA limit set
worst single sample: 63 µg/L | 171/198 | SYR4 | 2012–2019 |
| Bromodichloromethane | 23 µg/L No EPA limit set
worst single sample: 33 µg/L | 140/198 | SYR4 | 2012–2019 |
| Combined Uranium | 23.84 µg/L 79% of the EPA limit 30 µg/L
worst single sample: 25.33 µg/L | 130/138 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 11 µg/L No EPA limit set
worst single sample: 15 µg/L | 100/100 | SYR4 | 2013–2019 |
| Chloroform | 6.5 µg/L No EPA limit set
worst single sample: 9.4 µg/L | 96/194 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 17 µg/L 28% of the EPA limit 60 µg/L
worst single sample: 21 µg/L | 96/97 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 802000 µg/L 8020% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 1000000 µg/L | 88/192 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 3.56 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 65/83 | SYR4 | 2013–2019 |
| Barium | 140 µg/L 7% of the EPA limit 2000 µg/L
worst single sample: 170 µg/L | 61/195 | SYR4 | 2012–2019 |
| Arsenic | 4.11 µg/L 41% of the EPA limit 10 µg/L
worst single sample: 6.2 µg/L | 60/195 | SYR4 | 2012–2019 |
| Lead | 0.00051 mg/L 3.4% of the EPA limit 0.0150 mg/L | 53/53 | LCR | 2025 |
| Copper | 155.5 µg/L 12% of the EPA limit 1300 µg/L
worst single sample: 200 µg/L | 30/195 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.3 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 11/76 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 1.78 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 9/77 | SYR4 | 2013–2019 |
| Selenium | 14.04 µg/L 28% of the EPA limit 50 µg/L
worst single sample: 15 µg/L | 4/195 | SYR4 | 2012–2019 |
| Chromium | 27.1 µg/L 27% of the EPA limit 100 µg/L
worst single sample: 28 µg/L | 2/195 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 0.6745 µg/L 1% of the EPA limit 70 µg/L
worst single sample: 0.6800 µg/L | 2/213 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 5 pCi/L No EPA limit set | 1/3 | SYR4 | 2012–2019 |
| Thallium, Total | 1.1 µg/L 55% of the EPA limit 2 µg/L | 1/195 | SYR4 | 2012–2019 |
| Lithium | 36.9 µg/L No EPA limit set | 1/4 | UCMR-5 | 2024 |
86 contaminants tested, none detected
Utility contact
Frequently asked questions about Camp Pendleton (South)
Is Camp Pendleton (South) tap water safe to drink?
EPA monitoring detected 26 contaminants in Camp Pendleton (South)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Camp Pendleton (South)'s water?
EPA monitoring detected Fluoride, Nitrate, TTHM, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Camp Pendleton (South) serve?
Camp Pendleton (South) reports serving 42,219 people in California, per its EPA record.
Has Camp Pendleton (South) had any water quality violations?
The EPA has 33 violations on file for Camp Pendleton (South), of which 19 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.