Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2022-06-01 → 2022-06-30 |
| MCL | Health-based | Resolved | 2022-06-01 → 2022-06-30 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-10-31 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-10-31 |
| MR | Monitoring | Resolved | 2022-07-01 |
| MR | Monitoring | Resolved | 2022-07-01 |
| MR | Monitoring | Resolved | 2009-04-01 → 2010-03-31 |
| MR | Monitoring | Resolved | 2009-04-01 → 2010-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 21000 µg/L 210% of the EPA limit, in the worst sample — 10000 µg/L | 556/562 | SYR4 | 2012–2019 |
| Fluoride | 530 µg/L 13% of the EPA limit 4000 µg/L | 40/42 | SYR4 | 2012–2019 |
| TTHM | 15 µg/L 19% of the EPA limit 80 µg/L | 38/42 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.4 µg/L No EPA limit set | 37/46 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 37/37 | LCR | 2025 |
| Bromoform | 4.2 µg/L No EPA limit set | 33/47 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.6 µg/L No EPA limit set | 32/46 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 22 µg/L 37% of the EPA limit 60 µg/L | 28/40 | SYR4 | 2012–2019 |
| Chloroform | 4.2 µg/L No EPA limit set | 23/46 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 20 µg/L No EPA limit set | 23/40 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1000000 µg/L 10000% of the EPA limit, in the worst sample — 10000 µg/L | 21/21 | SYR4 | 2012–2019 |
| Combined Uranium | 11.3091 µg/L 38% of the EPA limit 30 µg/L | 19/19 | SYR4 | 2012–2017 |
| Barium | 240 µg/L 12% of the EPA limit 2000 µg/L | 15/29 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.7 µg/L No EPA limit set | 14/40 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.6 µg/L No EPA limit set | 10/40 | SYR4 | 2012–2019 |
| Chromium | 1.9 µg/L 1.9% of the EPA limit 100 µg/L | 6/29 | SYR4 | 2012–2019 |
| Lithium | 16.2 µg/L No EPA limit set | 6/19 | UCMR-5 | 2025 |
| Selenium | 6 µg/L 12% of the EPA limit 50 µg/L | 3/29 | SYR4 | 2012–2019 |
| Arsenic | 7.6 µg/L 76% of the EPA limit 10 µg/L | 2/32 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.1 µg/L No EPA limit set | 1/40 | SYR4 | 2012–2019 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Lake Hemet Mwd
Is Lake Hemet Mwd tap water safe to drink?
EPA monitoring detected 20 contaminants in Lake Hemet Mwd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Lake Hemet Mwd's water?
EPA monitoring detected Nitrate, Fluoride, TTHM, Dibromochloromethane, Lead, and others. The full list with the level and data source for each is above.
How many people does Lake Hemet Mwd serve?
Lake Hemet Mwd reports serving 52,913 people in California, per its EPA record.
Has Lake Hemet Mwd had any water quality violations?
The EPA has 8 violations on file for Lake Hemet Mwd, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.