Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2020-01-01 → 2020-03-06 |
| MR | Monitoring | Resolved | 2020-01-01 → 2020-03-06 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0053 µg/L | 1/16 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 16600 µg/L 166% of the EPA limit, in the worst sample — 10000 µg/L | 4372/4410 | SYR4 | 2012–2019 |
| Trichloroethylene | 6.1 µg/L 122% of the EPA limit, in the worst sample — 5 µg/L | 1222/1663 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 17 µg/L 340% of the EPA limit, in the worst sample — 5 µg/L | 1179/1685 | SYR4 | 2012–2019 |
| Dibromochloromethane | 17.2 µg/L No EPA limit set | 285/810 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17.1 µg/L No EPA limit set | 232/795 | SYR4 | 2012–2019 |
| Carbon Tetrachloride | 1.1 µg/L 22% of the EPA limit 5 µg/L | 232/1605 | SYR4 | 2012–2019 |
| Bromoform | 8.2 µg/L No EPA limit set | 203/832 | SYR4 | 2012–2019 |
| Chloroform | 15.9 µg/L No EPA limit set | 193/772 | SYR4 | 2012–2019 |
| TTHM | 43 µg/L 54% of the EPA limit 80 µg/L | 125/139 | SYR4 | 2012–2019 |
| Fluoride | 1080 µg/L 27% of the EPA limit 4000 µg/L | 123/123 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 29 µg/L 48% of the EPA limit 60 µg/L | 59/124 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 12 µg/L No EPA limit set | 51/124 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.8 µg/L No EPA limit set | 50/124 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 16000 µg/L 160% of the EPA limit, in the worst sample — 10000 µg/L | 38/38 | SYR4 | 2016–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 37/37 | LCR | 2023 |
| Trichloroacetic Acid | 13 µg/L No EPA limit set | 32/124 | SYR4 | 2012–2019 |
| Combined Uranium | 23.84 µg/L 79% of the EPA limit 30 µg/L | 25/25 | SYR4 | 2013–2019 |
| Chromium | 44 µg/L 44% of the EPA limit 100 µg/L | 23/135 | SYR4 | 2012–2019 |
| Arsenic | 2.9 µg/L 29% of the EPA limit 10 µg/L | 15/123 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 1.1 µg/L 1.6% of the EPA limit 70 µg/L | 5/1604 | SYR4 | 2012–2019 |
| Lithium | 91.9 µg/L No EPA limit set | 4/16 | UCMR-5 | 2025 |
| 1,2-Dichloropropane | 2.9 µg/L 58% of the EPA limit 5 µg/L | 3/1618 | SYR4 | 2012–2019 |
| Copper | 160 µg/L 12% of the EPA limit 1300 µg/L | 2/97 | SYR4 | 2012–2019 |
| Mercury | 2.1 µg/L 105% of the EPA limit, in the worst sample — 2 µg/L | 2/120 | SYR4 | 2012–2019 |
| Lead | 1 µg/L 6.7% of the EPA limit 15 µg/L | 1/97 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3 µg/L No EPA limit set | 1/124 | SYR4 | 2012–2019 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Cal/Am Water Company - San Marino
Is Cal/Am Water Company - San Marino tap water safe to drink?
EPA monitoring detected 27 contaminants in Cal/Am Water Company - San Marino's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cal/Am Water Company - San Marino's water?
EPA monitoring detected Nitrate, Trichloroethylene, Tetrachloroethylene, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Cal/Am Water Company - San Marino serve?
Cal/Am Water Company - San Marino reports serving 47,995 people in California, per its EPA record.
Has Cal/Am Water Company - San Marino had any water quality violations?
The EPA has 2 violations on file for Cal/Am Water Company - San Marino, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.