Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1997-02-01 → 1997-02-28 |
| MCL | Health-based | Resolved | 1997-02-01 → 1997-02-28 |
| MCL | Health-based | Resolved | 1992-05-01 → 1992-05-31 |
| MCL | Health-based | Resolved | 1992-05-01 → 1992-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromoform | 52.6 µg/L No EPA limit set | 127/140 | SYR4 | 2012–2019 |
| TTHM | 82.7 µg/L 103% of the EPA limit, in the worst sample — 80 µg/L | 127/128 | SYR4 | 2012–2019 |
| Nitrate | 8682.92 µg/L 87% of the EPA limit 10000 µg/L | 122/134 | SYR4 | 2012–2019 |
| Dibromochloromethane | 30.3 µg/L No EPA limit set | 121/140 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 22 µg/L 37% of the EPA limit 60 µg/L | 116/128 | SYR4 | 2012–2019 |
| Trichloroethylene | 39 µg/L 780% of the EPA limit, in the worst sample — 5 µg/L | 88/108 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17.7 µg/L No EPA limit set | 85/140 | SYR4 | 2012–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 82/82 | LCR | 2026 |
| Dibromoacetic Acid | 9.1 µg/L No EPA limit set | 80/92 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 9.2 µg/L No EPA limit set | 55/92 | SYR4 | 2014–2019 |
| Chloroform | 12.8 µg/L No EPA limit set | 48/140 | SYR4 | 2012–2019 |
| Barium | 120 µg/L 6% of the EPA limit 2000 µg/L | 29/29 | SYR4 | 2012–2019 |
| Fluoride | 410 µg/L 10% of the EPA limit 4000 µg/L | 29/29 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 4 µg/L No EPA limit set | 13/92 | SYR4 | 2014–2019 |
| Combined Uranium | 10.132 µg/L 34% of the EPA limit 30 µg/L | 11/12 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.6 µg/L No EPA limit set | 11/92 | SYR4 | 2014–2019 |
| Nitrate-Nitrite | 8200 µg/L 82% of the EPA limit 10000 µg/L | 8/16 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 6.5 µg/L No EPA limit set | 7/92 | SYR4 | 2014–2019 |
| Lithium | 27 µg/L No EPA limit set | 7/13 | UCMR-5 | 2025 |
| Gross Beta Particle Activity | 4.6 pCi/L No EPA limit set | 2/2 | SYR4 | 2019 |
| Lead | 8 µg/L 53% of the EPA limit 15 µg/L | 1/29 | SYR4 | 2012–2019 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Cal/Am Water Company - Baldwin Hills
Is Cal/Am Water Company - Baldwin Hills tap water safe to drink?
EPA monitoring detected 21 contaminants in Cal/Am Water Company - Baldwin Hills's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cal/Am Water Company - Baldwin Hills's water?
EPA monitoring detected Bromoform, TTHM, Nitrate, Dibromochloromethane, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Cal/Am Water Company - Baldwin Hills serve?
Cal/Am Water Company - Baldwin Hills reports serving 20,724 people in California, per its EPA record.
Has Cal/Am Water Company - Baldwin Hills had any water quality violations?
The EPA has 4 violations on file for Cal/Am Water Company - Baldwin Hills, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.