Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MCL | Health-based | Resolved | 1995-12-01 → 1995-12-31 |
| MR | Monitoring | Resolved | 2002-05-01 → 2002-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 11000 µg/L 110% of the EPA limit, in the worst sample — 10000 µg/L | 2212/2220 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 6.8 µg/L 136% of the EPA limit, in the worst sample — 5 µg/L | 505/1055 | SYR4 | 2012–2019 |
| Trichloroethylene | 1.5 µg/L 30% of the EPA limit 5 µg/L | 365/1055 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 2.3 µg/L 33% of the EPA limit 7 µg/L | 186/1055 | SYR4 | 2012–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 36/36 | LCR | 2025 |
| Combined Uranium | 40.23 µg/L 134% of the EPA limit, in the worst sample — 30 µg/L | 18/18 | SYR4 | 2012–2019 |
| Fluoride | 850 µg/L 21% of the EPA limit 4000 µg/L | 11/11 | SYR4 | 2012–2018 |
| TTHM | 14 µg/L 18% of the EPA limit 80 µg/L | 7/14 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 790000 µg/L 7900% of the EPA limit, in the worst sample — 10000 µg/L | 6/7 | SYR4 | 2012–2018 |
| Bromoform | 7.7 µg/L No EPA limit set | 5/14 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.3 µg/L No EPA limit set | 5/14 | SYR4 | 2012–2019 |
| Chromium | 12 µg/L 12% of the EPA limit 100 µg/L | 4/10 | SYR4 | 2012–2018 |
| Bromodichloromethane | 1.5 µg/L No EPA limit set | 3/14 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.1 µg/L No EPA limit set | 3/12 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 2.1 µg/L 3.5% of the EPA limit 60 µg/L | 3/12 | SYR4 | 2014–2019 |
| trans-1,2-Dichloroethylene | 0.5300 µg/L 0.5% of the EPA limit 100 µg/L | 1/36 | SYR4 | 2012–2019 |
95 contaminants tested, none detected
Utility contact
Frequently asked questions about Cal-Am Water Company - East Pasadena
Is Cal-Am Water Company - East Pasadena tap water safe to drink?
EPA monitoring detected 16 contaminants in Cal-Am Water Company - East Pasadena's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cal-Am Water Company - East Pasadena's water?
EPA monitoring detected Nitrate, Tetrachloroethylene, Trichloroethylene, 1,1-Dichloroethylene, Lead, and others. The full list with the level and data source for each is above.
How many people does Cal-Am Water Company - East Pasadena serve?
Cal-Am Water Company - East Pasadena reports serving 9,949 people in California, per its EPA record.
Has Cal-Am Water Company - East Pasadena had any water quality violations?
The EPA has 11 violations on file for Cal-Am Water Company - East Pasadena, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.