Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2024-10-17 |
| MCL | Health-based | Resolved | 2019-04-01 → 2019-06-30 |
| MCL | Health-based | Resolved | 2019-04-01 → 2019-06-30 |
| MCL | Health-based | Resolved | 2019-01-01 → 2019-03-31 |
| MCL | Health-based | Resolved | 2019-01-01 → 2019-03-31 |
| MCL | Health-based | Resolved | 2019-01-01 → 2019-03-31 |
| MCL | Health-based | Resolved | 2018-10-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2018-10-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2018-10-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2018-07-01 → 2018-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 81 µg/L 810% of the EPA limit, in the worst sample — 10 µg/L | 582/1995 | SYR4 | 2012–2019 |
| Nitrate | 23000 µg/L 230% of the EPA limit, in the worst sample — 10000 µg/L | 326/348 | SYR4 | 2012–2019 |
| Bromoform | 19 µg/L No EPA limit set | 83/108 | SYR4 | 2014–2019 |
| TTHM | 30 µg/L 38% of the EPA limit 80 µg/L | 65/108 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 100 µg/L 167% of the EPA limit, in the worst sample — 60 µg/L | 44/98 | SYR4 | 2014–2019 |
| Dibromochloromethane | 9.2 µg/L No EPA limit set | 33/108 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 9.2 µg/L No EPA limit set | 30/98 | SYR4 | 2014–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 28/28 | LCR | 2025 |
| Trichloroacetic Acid | 100 µg/L No EPA limit set | 19/98 | SYR4 | 2014–2019 |
| Barium | 180 µg/L 9% of the EPA limit 2000 µg/L | 14/14 | SYR4 | 2013–2019 |
| Fluoride | 700 µg/L 18% of the EPA limit 4000 µg/L | 14/14 | SYR4 | 2013–2019 |
| Tetrachloroethylene | 4.2 µg/L 84% of the EPA limit 5 µg/L | 8/42 | SYR4 | 2013–2019 |
| Bromodichloromethane | 1.5 µg/L No EPA limit set | 7/109 | SYR4 | 2014–2019 |
| Selenium | 4.2 µg/L 8.4% of the EPA limit 50 µg/L | 7/14 | SYR4 | 2013–2019 |
| 1,2-DIBROMO-3-CHLOROPROPANE | 0.2300 µg/L 115% of the EPA limit, in the worst sample — 0.2000 µg/L | 3/82 | SYR4 | 2013–2019 |
| Copper | 71 µg/L 5.5% of the EPA limit 1300 µg/L | 2/20 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 4.1 µg/L No EPA limit set | 2/98 | SYR4 | 2014–2019 |
| Lead | 2.9 µg/L 19% of the EPA limit 15 µg/L | 2/39 | SYR4 | 2013–2019 |
| Benzene | 0.6500 µg/L 13% of the EPA limit 5 µg/L | 1/69 | SYR4 | 2012–2019 |
| Combined Uranium | 0.4604 µg/L 1.5% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2013 |
| Di(2-ethylhexyl) Phthalate | 3.4 µg/L 57% of the EPA limit 6 µg/L | 1/7 | SYR4 | 2015–2016 |
| Mercury | 0.2400 µg/L 12% of the EPA limit 2 µg/L | 1/13 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 200000 µg/L 2000% of the EPA limit, in the worst sample — 10000 µg/L | 1/1 | SYR4 | 2013 |
| Nitrite | 110 µg/L 11% of the EPA limit 1000 µg/L | 1/14 | SYR4 | 2013–2019 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about Arvin Community Services Dist
Is Arvin Community Services Dist tap water safe to drink?
EPA monitoring detected 24 contaminants in Arvin Community Services Dist's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Arvin Community Services Dist's water?
EPA monitoring detected Arsenic, Nitrate, Bromoform, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Arvin Community Services Dist serve?
Arvin Community Services Dist reports serving 19,669 people in California, per its EPA record.
Has Arvin Community Services Dist had any water quality violations?
The EPA has 327 violations on file for Arvin Community Services Dist, of which 219 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.