← California

Tap water quality report

East Wilson Road Water Company

EPA monitoring tested this supplier for 50 contaminants and detected 6. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
6
detected
35
people served
56
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Kern

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

56
health-based violations
89
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
MCL Health-based Archived 2023-01-01 → 2023-03-31
MCL Health-based Archived 2022-04-01 → 2022-06-30
MCL Health-based Archived 2021-07-01 → 2021-09-30
MCL Health-based Archived 2021-04-01 → 2021-06-30
MCL Health-based Archived 2021-01-01 → 2021-03-31
MCL Health-based Archived 2020-10-01 → 2020-12-31
MCL Health-based Archived 2020-07-01 → 2020-09-30
MCL Health-based Archived 2020-04-01 → 2020-06-30
MCL Health-based Archived 2020-01-01 → 2020-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
15000 µg/L 150%
of the EPA limit, in the worst sample — 10000 µg/L
64/64 SYR4 2012–2019
Lead
0.0032 mg/L 21%
of the EPA limit 0.0150 mg/L
9/9 LCR 2023
Arsenic
5.2 µg/L 52%
of the EPA limit 10 µg/L
2/2 SYR4 2014–2017
Barium
39 µg/L 2%
of the EPA limit 2000 µg/L
2/2 SYR4 2014–2017
Selenium
6.4 µg/L 13%
of the EPA limit 50 µg/L
2/2 SYR4 2014–2017
Fluoride
130 µg/L 3.3%
of the EPA limit 4000 µg/L
1/2 SYR4 2014–2017
44 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBenzeneBeryllium, TotalChlorobenzeneCopperCadmiumCarbofuranCarbon TetrachlorideChromiumDichloromethaneDalaponDinosebEthylene DibromideEndothallEthylbenzeneLassoLeadMercuryNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PRICE, JACEN
Phone
661-332-7543
Email
jacenprice@gmail.com

Frequently asked questions about East Wilson Road Water Company

Is East Wilson Road Water Company tap water safe to drink?

EPA monitoring detected 6 contaminants in East Wilson Road Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in East Wilson Road Water Company's water?

EPA monitoring detected Nitrate, Lead, Arsenic, Barium, Selenium, and others. The full list with the level and data source for each is above.

How many people does East Wilson Road Water Company serve?

East Wilson Road Water Company reports serving 35 people in California, per its EPA record.

Has East Wilson Road Water Company had any water quality violations?

The EPA has 89 violations on file for East Wilson Road Water Company, of which 56 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.