← California

Tap water quality report

Maher Mutual Water Company

EPA monitoring tested this supplier for 74 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

74
contaminants tested
12
detected
140
people served
125
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Kern

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

125
health-based violations
161
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-01-01 → 2019-03-31
MCL Health-based Resolved 2019-01-01 → 2019-03-31
MCL Health-based Resolved 2018-10-01 → 2018-12-31
MCL Health-based Resolved 2018-10-01 → 2018-12-31
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
26 µg/L 260%
of the EPA limit, in the worst sample — 10 µg/L
38/38 SYR4 2012–2019
Nitrate
4746 µg/L 47%
of the EPA limit 10000 µg/L
20/20 SYR4 2012–2019
Lead
0.0019 mg/L 13%
of the EPA limit 0.0150 mg/L
10/10 LCR 2023
Fluoride
350 µg/L 8.8%
of the EPA limit 4000 µg/L
2/2 SYR4 2014–2017
1,2-DIBROMO-3-CHLOROPROPANE
0.1300 µg/L 65%
of the EPA limit 0.2000 µg/L
1/9 SYR4 2013–2019
Barium
18 µg/L 0.9%
of the EPA limit 2000 µg/L
1/2 SYR4 2014–2017
Copper
65 µg/L 5%
of the EPA limit 1300 µg/L
1/2 SYR4 2014–2017
Chloroform
1.6 µg/L
No EPA limit set
1/2 SYR4 2016–2019
Ethylene Dibromide
0.1900 µg/L 380%
of the EPA limit, in the worst sample — 0.0500 µg/L
1/15 SYR4 2013–2019
Lead
4.6 µg/L 31%
of the EPA limit 15 µg/L
1/2 SYR4 2014–2017
Total Haloacetic Acids (HAA5)
1.3 µg/L 2.2%
of the EPA limit 60 µg/L
1/2 SYR4 2016–2019
Trichloroacetic Acid
1.3 µg/L
No EPA limit set
1/2 SYR4 2016–2019
62 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDichloroacetic AcidDinosebEndothallEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
VAN SCOY, JEFF
Phone
661-573-8299
Email
mahermwc@gmail.com

Frequently asked questions about Maher Mutual Water Company

Is Maher Mutual Water Company tap water safe to drink?

EPA monitoring detected 12 contaminants in Maher Mutual Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Maher Mutual Water Company's water?

EPA monitoring detected Arsenic, Nitrate, Lead, Fluoride, 1,2-DIBROMO-3-CHLOROPROPANE, and others. The full list with the level and data source for each is above.

How many people does Maher Mutual Water Company serve?

Maher Mutual Water Company reports serving 140 people in California, per its EPA record.

Has Maher Mutual Water Company had any water quality violations?

The EPA has 161 violations on file for Maher Mutual Water Company, of which 125 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.