← California

Tap water quality report

Elm Court

EPA monitoring tested this supplier for 45 contaminants and detected 7. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

45
contaminants tested
7
detected
64
people served
7
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Fresno

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

7
health-based violations
143
violations on file
13
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
MCL Health-based Resolved 2014-07-01 → 2014-07-31
MCL Health-based Resolved 2014-07-01 → 2014-07-31
MCL Health-based Resolved 2013-08-01 → 2013-08-31
MCL Health-based Resolved 2013-08-01 → 2013-08-31
MCL Health-based Resolved 2012-11-01 → 2012-11-30
MCL Health-based Resolved 2012-11-01 → 2012-11-30
RPT Monitoring Unaddressed 2024-10-17
Other Monitoring Addressed 2024-07-01
MR Monitoring Resolved 2024-01-01 → 2024-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
7/7 LCR 2022
Arsenic
8.985 µg/L 90%
of the EPA limit 10 µg/L
worst single sample: 9 µg/L
2/2 SYR4 2014–2019
Barium
10.805 µg/L 0.5%
of the EPA limit 2000 µg/L
worst single sample: 11 µg/L
2/2 SYR4 2014–2019
Fluoride
209 µg/L 5.2%
of the EPA limit 4000 µg/L
worst single sample: 210 µg/L
2/2 SYR4 2014–2019
Nitrate
1400 µg/L 14%
of the EPA limit 10000 µg/L
2/10 SYR4 2012–2019
Copper
2.5 µg/L 0.2%
of the EPA limit 1300 µg/L
1/2 SYR4 2014–2019
Nitrite
770 µg/L 77%
of the EPA limit 1000 µg/L
1/2 SYR4 2014–2019
38 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalAtrazineBenzeneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCadmiumCarbon TetrachlorideChromiumDichloromethaneDibromochloromethaneEthylene DibromideEthylbenzeneLassoLeadMercurySeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PEDIANO, JOVANA
Phone
559-478-4661
Email
Jdh_maintenance@yahoo.com

Frequently asked questions about Elm Court

Is Elm Court tap water safe to drink?

EPA monitoring detected 7 contaminants in Elm Court's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Elm Court's water?

EPA monitoring detected Lead, Arsenic, Barium, Fluoride, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Elm Court serve?

Elm Court reports serving 64 people in California, per its EPA record.

Has Elm Court had any water quality violations?

The EPA has 143 violations on file for Elm Court, of which 7 are health-based (a contaminant limit or required treatment was breached) and 13 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.