Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2004-01-01 → 2004-03-31 |
| MCL | Health-based | Resolved | 2003-01-01 → 2003-03-31 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 2001-07-01 → 2001-09-30 |
| MCL | Health-based | Resolved | 2001-04-01 → 2001-06-30 |
| MCL | Health-based | Resolved | 2000-04-01 → 2000-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 7.4 µg/L 74% of the EPA limit 10 µg/L | 86/171 | SYR4 | 2012–2019 |
| Nitrate | 880 µg/L 8.8% of the EPA limit 10000 µg/L | 60/76 | SYR4 | 2012–2019 |
| Copper | 450 µg/L 35% of the EPA limit 1300 µg/L | 33/33 | SYR4 | 2014–2017 |
| Lead | 7.5 µg/L 50% of the EPA limit 15 µg/L | 14/33 | SYR4 | 2014–2017 |
| Barium | 410 µg/L 21% of the EPA limit 2000 µg/L | 11/11 | SYR4 | 2012–2018 |
| Fluoride | 420 µg/L 11% of the EPA limit 4000 µg/L | 11/11 | SYR4 | 2012–2018 |
| TTHM | 19.2 µg/L 24% of the EPA limit 80 µg/L | 10/13 | SYR4 | 2012–2019 |
| Lithium | 216 µg/L No EPA limit set | 10/10 | UCMR-5 | 2023 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2023 |
| Chromium | 4.6 µg/L 4.6% of the EPA limit 100 µg/L | 7/11 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 2.8 µg/L 4.7% of the EPA limit 60 µg/L | 5/13 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 850 µg/L 8.5% of the EPA limit 10000 µg/L | 4/5 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 0.3000 pCi/L 6% of the EPA limit 5 pCi/L | 2/12 | SYR4 | 2012–2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about Arizona Water Co - Rimrock
Is Arizona Water Co - Rimrock tap water safe to drink?
EPA monitoring detected 13 contaminants in Arizona Water Co - Rimrock's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Arizona Water Co - Rimrock's water?
EPA monitoring detected Arsenic, Nitrate, Copper, Lead, Barium, and others. The full list with the level and data source for each is above.
How many people does Arizona Water Co - Rimrock serve?
Arizona Water Co - Rimrock reports serving 3,423 people in Arizona, per its EPA record.
Has Arizona Water Co - Rimrock had any water quality violations?
The EPA has 205 violations on file for Arizona Water Co - Rimrock, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.