Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Combined Uranium | 40.7916 µg/L 136% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 44.998 µg/L | 30/31 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 16.465 pCi/L 329% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 20.6 pCi/L | 28/31 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 14.075 pCi/L 94% of the EPA limit 15 pCi/L
worst single sample: 19.9 pCi/L | 26/31 | SYR4 | 2012–2019 |
| Arsenic | 12.45 µg/L 124% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 15 µg/L | 18/28 | SYR4 | 2012–2019 |
| Nitrate | 3900 µg/L 39% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2026 |
| Copper | 28.5 µg/L 2.2% of the EPA limit 1300 µg/L
worst single sample: 31 µg/L | 6/10 | SYR4 | 2014–2017 |
| TTHM | 8.67 µg/L 11% of the EPA limit 80 µg/L
worst single sample: 9.3 µg/L | 4/4 | SYR4 | 2013–2016 |
| Total Haloacetic Acids (HAA5) | 4.06 µg/L 6.8% of the EPA limit 60 µg/L
worst single sample: 4.3 µg/L | 3/4 | SYR4 | 2013–2016 |
| Lead | 9.555 µg/L 64% of the EPA limit 15 µg/L
worst single sample: 10 µg/L | 2/10 | SYR4 | 2014–2017 |
| Barium | 280 µg/L 14% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2013 |
| Fluoride | 3000 µg/L 75% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2013 |
| Nitrate-Nitrite | 3800 µg/L 38% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2013 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Ranch Water Service Inc
Is Ranch Water Service Inc tap water safe to drink?
EPA monitoring detected 13 contaminants in Ranch Water Service Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ranch Water Service Inc's water?
EPA monitoring detected Combined Uranium, Combined Radium (-226 And -228), Gross Alpha, Excl. Radon And U, Arsenic, Nitrate, and others. The full list with the level and data source for each is above.
How many people does Ranch Water Service Inc serve?
Ranch Water Service Inc reports serving 135 people in Arizona, per its EPA record.
Has Ranch Water Service Inc had any water quality violations?
The EPA has 862 violations on file for Ranch Water Service Inc, of which 172 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.