Tap water quality report

Buckeye City of

EPA monitoring tested this supplier for 101 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

101
contaminants tested
14
detected
7,008
people served
16
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Maricopa

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

16
health-based violations
250
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2006-09-01 → 2006-09-30
MCL Health-based Resolved 2005-10-01 → 2005-10-31
MCL Health-based Resolved 2005-08-01 → 2005-08-31
MCL Health-based Resolved 2005-02-01 → 2005-02-28
MCL Health-based Resolved 2004-07-01 → 2004-09-30
MCL Health-based Resolved 2004-04-01 → 2004-06-30
MCL Health-based Resolved 2004-01-01 → 2004-03-31
MCL Health-based Resolved 2003-10-01 → 2003-12-31
MCL Health-based Resolved 2003-09-01 → 2003-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
10000 µg/L 100%
of the EPA limit 10000 µg/L
120/122 SYR4 2012–2019
Copper
1500 µg/L 115%
of the EPA limit, in the worst sample — 1300 µg/L
60/60 SYR4 2012–2018
TTHM
16.9 µg/L 21%
of the EPA limit 80 µg/L
18/18 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
12/12 LCR 2024
Total Haloacetic Acids (HAA5)
4.62 µg/L 7.7%
of the EPA limit 60 µg/L
6/18 SYR4 2012–2019
Lead
2.2 µg/L 15%
of the EPA limit 15 µg/L
5/59 SYR4 2012–2018
Arsenic
9 µg/L 90%
of the EPA limit 10 µg/L
4/4 SYR4 2018
Barium
252 µg/L 13%
of the EPA limit 2000 µg/L
4/4 SYR4 2018
Chromium
32.2 µg/L 32%
of the EPA limit 100 µg/L
4/4 SYR4 2018
Fluoride
1160 µg/L 29%
of the EPA limit 4000 µg/L
4/4 SYR4 2018
Di(2-ethylhexyl) Phthalate
0.9500 µg/L 16%
of the EPA limit 6 µg/L
2/6 SYR4 2018
Nitrate-Nitrite
6800 µg/L 68%
of the EPA limit 10000 µg/L
2/2 SYR4 2012
Selenium
8.3 µg/L 17%
of the EPA limit 50 µg/L
2/4 SYR4 2018
Lithium
91 µg/L
No EPA limit set
2/2 UCMR-5 2025
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Frequently asked questions about Buckeye City of

Is Buckeye City of tap water safe to drink?

EPA monitoring detected 14 contaminants in Buckeye City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Buckeye City of's water?

EPA monitoring detected Nitrate, Copper, TTHM, Lead, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Buckeye City of serve?

Buckeye City of reports serving 7,008 people, per its EPA record.

Has Buckeye City of had any water quality violations?

The EPA has 250 violations on file for Buckeye City of, of which 16 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.