← Arkansas

Tap water quality report

North Jackson Co Rural Water Assn

EPA monitoring tested this supplier for 11 contaminants and detected 9. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

11
contaminants tested
9
detected
807
people served
5
health-based violations
Water source
GWP
Ownership
Local government
Counties served
Jackson

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
55
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2005-05-01 → 2005-05-31
MCL Health-based Resolved 2005-05-01 → 2005-05-31
MCL Health-based Resolved 2005-05-01 → 2005-05-31
MCL Health-based Resolved 2005-05-01 → 2005-05-31
MCL Health-based Archived 1993-08-01 → 1993-08-31
Other Monitoring Unaddressed 2025-07-01
RPT Monitoring Resolved 2023-04-01
Other Monitoring Unaddressed 2021-07-01
Other Monitoring Resolved 2016-07-01
Other Monitoring Resolved 2011-10-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
18.925 µg/L
No EPA limit set
worst single sample: 19.2 µg/L
12/12 SYR4 2014–2019
Bromoform
6.045 µg/L
No EPA limit set
worst single sample: 6.1 µg/L
12/12 SYR4 2014–2019
Chloroform
16.07 µg/L
No EPA limit set
worst single sample: 16.4 µg/L
12/12 SYR4 2014–2019
Dibromoacetic Acid
3.6 µg/L
No EPA limit set
12/12 SYR4 2014–2019
Dibromochloromethane
18.225 µg/L
No EPA limit set
worst single sample: 18.5 µg/L
12/12 SYR4 2014–2019
Dichloroacetic Acid
6 µg/L
No EPA limit set
12/12 SYR4 2014–2019
TTHM
55.45 µg/L 69%
of the EPA limit 80 µg/L
worst single sample: 56 µg/L
12/12 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
11.65 µg/L 19%
of the EPA limit 60 µg/L
worst single sample: 12.2 µg/L
12/12 SYR4 2014–2019
Trichloroacetic Acid
3.265 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
10/12 SYR4 2014–2019
2 contaminants tested, none detected
Monobromoacetic AcidMonochloroacetic Acid

Utility contact

Contact
HASKETT, JOHNNY
Phone
870-349-2338
Email
TUCKERMANWS@YAHOO.COM

Frequently asked questions about North Jackson Co Rural Water Assn

Is North Jackson Co Rural Water Assn tap water safe to drink?

EPA monitoring detected 9 contaminants in North Jackson Co Rural Water Assn's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in North Jackson Co Rural Water Assn's water?

EPA monitoring detected Bromodichloromethane, Bromoform, Chloroform, Dibromoacetic Acid, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does North Jackson Co Rural Water Assn serve?

North Jackson Co Rural Water Assn reports serving 807 people in Arkansas, per its EPA record.

Has North Jackson Co Rural Water Assn had any water quality violations?

The EPA has 55 violations on file for North Jackson Co Rural Water Assn, of which 5 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.