← Arkansas

Tap water quality report

Helena Water Sewer

EPA monitoring tested this supplier for 107 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

107
contaminants tested
17
detected
2,708
people served
84
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Phillips

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

84
health-based violations
124
violations on file
3
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2026-04-30
TT Health-based Resolved 2024-07-01
TT Health-based Resolved 2024-07-01
TT Health-based Resolved 2024-07-01
TT Health-based Resolved 2024-07-01
TT Health-based Resolved 2024-06-01
TT Health-based Resolved 2024-06-01
TT Health-based Resolved 2024-06-01
TT Health-based Resolved 2024-06-01
TT Health-based Resolved 2024-05-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
901.5 µg/L 23%
of the EPA limit 4000 µg/L
worst single sample: 1100 µg/L
98/98 SYR4 2012–2019
Lead
8.49 µg/L 57%
of the EPA limit 15 µg/L
worst single sample: 26 µg/L
27/46 SYR4 2014–2017
Copper
617 µg/L 47%
of the EPA limit 1300 µg/L
worst single sample: 750 µg/L
24/44 SYR4 2014–2017
Dibromochloromethane
14.54 µg/L
No EPA limit set
worst single sample: 16.7 µg/L
19/20 SYR4 2012–2019
Bromodichloromethane
7.8 µg/L
No EPA limit set
14/14 SYR4 2014–2019
Lead
0.0090 mg/L 60%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Bromoform
18.38 µg/L
No EPA limit set
worst single sample: 18.8 µg/L
13/14 SYR4 2014–2019
Chloroform
3.34 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
13/14 SYR4 2014–2019
TTHM
44.145 µg/L 55%
of the EPA limit 80 µg/L
worst single sample: 45.3 µg/L
12/12 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
10.195 µg/L 17%
of the EPA limit 60 µg/L
worst single sample: 10.3 µg/L
8/12 SYR4 2014–2019
Dibromoacetic Acid
6.95 µg/L
No EPA limit set
worst single sample: 7.1 µg/L
7/12 SYR4 2014–2019
Trichloroacetic Acid
3.13 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
7/12 SYR4 2014–2019
Dichloroacetic Acid
3.375 µg/L
No EPA limit set
worst single sample: 3.8 µg/L
6/12 SYR4 2014–2019
Lithium
36 µg/L
No EPA limit set
2/2 UCMR-5 2024
Barium
280 µg/L 14%
of the EPA limit 2000 µg/L
1/2 SYR4 2014–2017
Di(2-ethylhexyl) Phthalate
5.07 µg/L 85%
of the EPA limit 6 µg/L
1/12 SYR4 2012–2019
Gross Beta Particle Activity
7.1 pCi/L
No EPA limit set
1/7 SYR4 2014–2017
90 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitrate-NitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ROSE, SAEED
Phone
870-817-7439
Email
SAEEDROSE04@GMAIL.COM

Frequently asked questions about Helena Water Sewer

Is Helena Water Sewer tap water safe to drink?

EPA monitoring detected 17 contaminants in Helena Water Sewer's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Helena Water Sewer's water?

EPA monitoring detected Fluoride, Lead, Copper, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Helena Water Sewer serve?

Helena Water Sewer reports serving 2,708 people in Arkansas, per its EPA record.

Has Helena Water Sewer had any water quality violations?

The EPA has 124 violations on file for Helena Water Sewer, of which 84 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.