← Pennsylvania

Tap water quality report

Johnsonburg, PA

EPA monitoring detected 18 contaminants across the 1 water supplier serving Johnsonburg. A detection doesn't automatically mean the water is unsafe — see the highest level found for each below, with its EPA source and period.

1
water supplier
2,413
people served
18
contaminants found

What was found in Johnsonburg's water

The highest level seen across the city's suppliers, the EPA limit for each, and where the figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Copper
1880 µg/L 145%
of the EPA limit, in the worst sample — 1300 µg/L
1/1 SYR4
Total Haloacetic Acids (HAA5)
1100 µg/L 1833%
of the EPA limit, in the worst sample — 60 µg/L
1/1 SYR4
Monochloroacetic Acid
1000 µg/L
No EPA limit set
1/1 SYR4
Nitrate
462 µg/L 4.6%
of the EPA limit 10000 µg/L
1/1 SYR4
TTHM
161 µg/L 201%
of the EPA limit, in the worst sample — 80 µg/L
1/1 SYR4
Barium
157 µg/L 7.9%
of the EPA limit 2000 µg/L
1/1 SYR4
Chloroform
115 µg/L
No EPA limit set
1/1 SYR4
Bromoform
111 µg/L
No EPA limit set
1/1 SYR4
Fluoride
110 µg/L 2.8%
of the EPA limit 4000 µg/L
1/1 SYR4
Trichloroacetic Acid
53.2 µg/L
No EPA limit set
1/1 SYR4
Dichloroacetic Acid
47.3 µg/L
No EPA limit set
1/1 SYR4
Dibromoacetic Acid
32.9 µg/L
No EPA limit set
1/1 SYR4
Bromodichloromethane
32 µg/L
No EPA limit set
1/1 SYR4
Dibromochloromethane
31 µg/L
No EPA limit set
1/1 SYR4
Monobromoacetic Acid
19.9 µg/L
No EPA limit set
1/1 SYR4
Lead
18.5 µg/L 123%
of the EPA limit, in the worst sample — 15 µg/L
1/1 SYR4
Lead
0.1612 mg/L 1075%
above the EPA limit of 0.0150 mg/L
1/1 LCR
Mercury
0.0730 µg/L 3.7%
of the EPA limit 2 µg/L
1/1 SYR4
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Johnsonburg

SupplierPopulation served
JOHNSONBURG MUNICIPAL AUTH 2,413

Frequently asked questions about Johnsonburg tap water

Is Johnsonburg tap water safe to drink?

EPA testing detected 18 contaminants in the water serving Johnsonburg. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Johnsonburg?

1 public water supplier report drinking-water monitoring for Johnsonburg, Pennsylvania to the EPA. Each is listed above with its population served.

What contaminants are in Johnsonburg's water?

The contaminants EPA monitoring detected in Johnsonburg include Copper, Total Haloacetic Acids (HAA5), Monochloroacetic Acid, Nitrate, TTHM. The full list, with the highest level found and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.