What was found in Columbiana's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Nitrate | 331 µg/L 3.3% of the EPA limit 10000 µg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019
Highest in the city: 2570 µg/L — BREEZEWAY MOBILE MANOR · 46 people · 2019 | 2/2 | SYR4 |
| Nitrate-Nitrite | 2160 µg/L 22% of the EPA limit 10000 µg/L Highest in the city: BREEZEWAY MOBILE MANOR · 46 people · 2018 | 1/2 | SYR4 |
| Fluoride | 1034.5 µg/L 26% of the EPA limit 4000 µg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2017 | 2/2 | SYR4 |
| Copper | 12.999 µg/L 1% of the EPA limit 1300 µg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2017
Highest in the city: 116.92 µg/L — BREEZEWAY MOBILE MANOR · 46 people · 2017 | 2/2 | SYR4 |
| Barium | 21.3 µg/L 1.1% of the EPA limit 2000 µg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2017
Highest in the city: 49.45 µg/L — BREEZEWAY MOBILE MANOR · 46 people · 2017 | 2/2 | SYR4 |
| Lead | 40.4785 µg/L 270% of the EPA limit, at the 95th percentile of samples — 15 µg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2017 | 1/2 | SYR4 |
| TTHM | 26.305 µg/L 33% of the EPA limit 80 µg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Total Haloacetic Acids (HAA5) | 13.68 µg/L 23% of the EPA limit 60 µg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Lithium | 11 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2025 | 1/2 | UCMR-5 |
| Bromoform | 10.5575 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Gross Beta Particle Activity | 9.24 pCi/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2017 | 1/2 | SYR4 |
| Dibromochloromethane | 8.8 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Monobromoacetic Acid | 1.0995 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019
Highest in the city: 8.2 µg/L — BREEZEWAY MOBILE MANOR · 46 people · 2019 | 2/2 | SYR4 |
| Dibromoacetic Acid | 7.5565 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Bromodichloromethane | 5.0025 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Chloroform | 4.926 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Trichloroacetic Acid | 3.54 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019 | 2/2 | SYR4 |
| Dichloroacetic Acid | 2.06 µg/L No EPA limit set Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2019
Highest in the city: 2.995 µg/L — BREEZEWAY MOBILE MANOR · 46 people · 2019 | 2/2 | SYR4 |
| Combined Radium (-226 And -228) | 1.8 pCi/L 36% of the EPA limit 5 pCi/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2017 | 1/2 | SYR4 |
| Monochloroacetic Acid | 1.22 µg/L No EPA limit set Highest in the city: BREEZEWAY MOBILE MANOR · 46 people · 2019 | 1/2 | SYR4 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L Main supplier: COLUMBIANA CITY PWS · 6,727 people · 2023 | 2/2 | LCR |
Water suppliers serving Columbiana
| Supplier | Population served |
|---|---|
| COLUMBIANA CITY PWS | 6,727 |
| BREEZEWAY MOBILE MANOR | 46 |
Frequently asked questions about Columbiana tap water
Is Columbiana tap water safe to drink?
EPA testing detected 21 contaminants in the water serving Columbiana. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Columbiana?
2 public water suppliers report drinking-water monitoring for Columbiana, Ohio to the EPA. Each is listed above with its population served.
What contaminants are in Columbiana's water?
The contaminants EPA monitoring detected in Columbiana include Nitrate, Nitrate-Nitrite, Fluoride, Copper, Barium. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.