← New Jersey

Tap water quality report

South Brunswick twp.-1221, NJ

EPA monitoring detected 31 contaminants across the 1 water supplier serving South Brunswick twp.-1221. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

1
water supplier
45,450
people served
31
contaminants found

What was found in South Brunswick twp.-1221's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate-Nitrite
3500 µg/L 35%
of the EPA limit 10000 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2013
1/1 SYR4
Nitrate
3320 µg/L 33%
of the EPA limit 10000 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Fluoride
900 µg/L 23%
of the EPA limit 4000 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Copper
356.75 µg/L 27%
of the EPA limit 1300 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Barium
283.5 µg/L 14%
of the EPA limit 2000 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
TTHM
74.36 µg/L 93%
of the EPA limit 80 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Chloroform
59.625 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Total Haloacetic Acids (HAA5)
35.275 µg/L 59%
of the EPA limit 60 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Trichloroacetic Acid
22.03 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Dichloroacetic Acid
13.66 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Bromodichloromethane
12.98 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Gross Alpha, Excl. Radon And U
10.85 pCi/L 72%
of the EPA limit 15 pCi/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2018
1/1 SYR4
Lead
10.69 µg/L 71%
of the EPA limit 15 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Dibromoacetic Acid
10.4455 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Selenium
6 µg/L 12%
of the EPA limit 50 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Chromium
4.75 µg/L 4.8%
of the EPA limit 100 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Combined Uranium
4.3343 µg/L 14%
of the EPA limit 30 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2018
1/1 SYR4
Beryllium, Total
3.968 µg/L 99%
of the EPA limit 4 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Combined Radium (-226 And -228)
3.266 pCi/L 65%
of the EPA limit 5 pCi/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Dibromochloromethane
3.244 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Thallium, Total
2.3255 µg/L 116%
of the EPA limit, at the 95th percentile of samples — 2 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Bromoform
1.3805 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Arsenic
0.7900 µg/L 7.9%
of the EPA limit 10 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
Antimony, Total
0.4830 µg/L 8.1%
of the EPA limit 6 µg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2019
1/1 SYR4
PFOA
0.0230 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2024
1/1 UCMR-5
Pfba
0.0130 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2024
1/1 UCMR-5
Pfpea
0.0095 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2024
1/1 UCMR-5
Pfhxa
0.0088 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2024
1/1 UCMR-5
Pfhpa
0.0069 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2024
1/1 UCMR-5
PFBS
0.0038 µg/L
No EPA limit set
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2024
1/1 UCMR-5
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
Main supplier: SOUTH BRUNSWICK TWP W DI · 45,450 people · 2026
1/1 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving South Brunswick twp.-1221

SupplierPopulation served
SOUTH BRUNSWICK TWP W DI 45,450

Frequently asked questions about South Brunswick twp.-1221 tap water

Is South Brunswick twp.-1221 tap water safe to drink?

EPA testing detected 31 contaminants in the water serving South Brunswick twp.-1221. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve South Brunswick twp.-1221?

1 public water supplier report drinking-water monitoring for South Brunswick twp.-1221, New Jersey to the EPA. Each is listed above with its population served.

What contaminants are in South Brunswick twp.-1221's water?

The contaminants EPA monitoring detected in South Brunswick twp.-1221 include Nitrate-Nitrite, Nitrate, Fluoride, Copper, Barium. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.